SANDI 50KW off grid inverter 480V dc to ac solar inverter with CSA/UL1741

SANDI 50KW off grid inverter 480V dc to ac solar inverter with CSA/UL1741

Model No.︰SDP-50KW

Brand Name︰SANDI

Country of Origin︰China

Unit Price︰US $ 9800 / pc

Minimum Order︰1 pc

Inquire Now

Product Description

SANDI 50KW off grid inverter 480V dc to ac solar

inverter with CSA/UL1741

 

Product Introduction                             

SANDI SDP series Pure Sine Wave Inverter is the one of the most advanced technology DC to AC conversion products in the world, it’s suitable use for areas without electricity, providing a complete power solution for strict demand applications. With SVPWM technology it has high conversion efficiency, high instantaneous power and low losses power output pure sine wave, applying to capacitive, inductive and nonlinear mixed-load, with superior load capacity, perfect protection function: overload, short circuit, low/over battery voltage, improper operation etc, which won’t cause mechanical failures. This Inverter is very suitable for solar power systems, wind power generation systems, wind and solar hybrid generation systems. The inverter can supply AC power to all kinds of electric equipment, air conditioners, electric motors, refrigerators, fluorescent lights, televisions, electric fans and other industrial power supply.

Technical Features:

1, Using the sixth generation efficient IPM intelligent module from Japanese Mitsubishi, high efficiency and stable performance. It with powerful protection function, the protection for short circuit, over load, over temperature is more safe and reliable. It’s service life can up to 15 years or more.

2, Intelligentized, modularized, simple structure design easy to maintenance.

3, According to the product configuration conditions, adjustment the system usage mode: DC(Battery/Solar) priority or AC mains bypass priority can be set.

4, Two kinds of start mode: Reduction Voltage Start and Variable Frequency Start. Customers can set start mode according to the type of their load. This function is very convenient for users and also reduce frequency converter’s usage, which reduced the cost of equipment investment, easy to connect wires and control.

5, The output frequency can be setting via LCD panel, it’s very convenient for customer.

6, The output voltage can be set between -40 % to +20 % of rated voltage. And the output voltage is very accuracy ±1%.

7, The DC input voltage range can be set. Over-voltage point, under-voltage point, over-voltage recovery point, under-voltage recovery point all can be setting via the LCD panel.

8, Pure sine wave output. With good dynamic response less than 50MS, waveform distortion rate smaller, higher conversion efficiency and stable output voltage.

9, Built-in low frequency isolation transformer, strong impact resistance, available with motors, pump, air conditioners and other high impact equipment. At the same time DC busbar and AC busbar are completely isolated to avoid interference.

10, Wide input voltage can be set according to customer’s requirement. Input voltage range can be selected from 100-300V, 200-500V or 500-850V, suitable for solar/wind system without backup batteries, it can save many cost and maximization use the solar/wind energy.

11, Using SVPWM space vector algorithms, high conversion efficiency, high instantaneous power and low losses conversion efficiency up to 94%.

12, Powerful data display function. LCD can display the DC input voltage, output frequency, phase voltage, phase current, AC bypass input voltage, output power KWH, time and date, temperature, fault code display.

13, European CE (EMC, LVD) and ISO9001 certificate

[Optional]

RS485 remote monitoring;

Can addAC bypass input complementary function;

Technical Parameter

Model

SDP-40KW

SDP-50KW

Isolation mode

Low Frequency Transformer

DC Input

Rated voltage (Vdc)

360Vdc

384Vdc

360Vdc

384Vdc

Rated current (A)

111A

104A

139A

130A

Input voltage range (Vdc)

324~480V

345~550V

324~480V

345~550V

AC Output

Rated power (Kw)

40KW

50KW

Rated voltage

220V±3%

380V±3%

380V±3%

Number of phases

1 phase 2 wire

3 phase 4 wire

3 phase 4 wire

Rated current (A)

182A

60A

76A

Rated output voltage range (V)

220/230/240/380/400/415/440/480VAC (optional)

Output frequency

50Hz or 60Hz ±0.05 (Can set)

Waveform

Pure sine wave

Waveform distortion rate (THD)

Linear load≤2%

Dynamic Response time (Load 0←→100%)

5%, ≤50ms

Power Factor (PF)

0.99

Inverter Efficiency

>93%

Electrical insulation properties

2000Vac1 Minute

Protection Function

Overload Ability

150%10s

Protection

Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc.

Display

LCD+LED

Communication interface (optional)

RS485 (AB)

Method of working

Working continuously

Cooling method

Fan-cooled

Short-circuit protection

No automatic recovery, need to restart the machine

Working Environment & Mechanical dimension

Degree of protection

IP20 (indoor)

Working Altitudem

≤3000m

Working temperature ()

-20+50

Relative humidity ()

0~90%, No condensation

Noise ( 1 meter)

≤55dB

Unit size: (W x D x H)

750×650×1200mm

Reference weight(Kg)

320Kg

360Kg

Our company can adjust parameter configuration according to users requirement.

 

Price Terms︰ FOB

Payment Terms︰ TT

Lead Time︰ 7-9 days

Standards Certificate︰ CE, ISO9001

Product Image